Nokta Industrial
 Automation Systems
Quick Answers


System Limits in Logging for Simatic Panels (WinCC Flexible). Keywords: WinCC Flexible, Tag Logging April 2008

The following system limits apply to Windows-based systems:
 
  xP270 xP277, Mobile Panel277 MP370 PC
Number of logs 20 20 50 100
Number of loggable tags per log 20 20 50 100

Number of log segments

400 400 400 400
Entries per log *) 10,000 10,000 50,000 500,000
*) Note for CE devices (xP 270, xP 277, MP 370, Mobile Panel 277): The operator panels are primarily not designed for logging data cyclically, they are more intended for logging acyclic error states (e.g. fault alarms and process signals). Operator panels are not designed for extensive logging tasks with large volumes of data or with high performance requirements.

Info, tips and examples of logging

Info:
Maximum write access to CF /MMC/SD cards and USB sticks.
Please note that CF/MMC/SD cards and USB sticks currently only allow a maximum guarantee of 100,000 write accesses (for CF cards) to 1,000,000 (for USB sticks). The specified maximum number of write accesses might vary from manufacturer to manufacturer and change in the course of time.