Determining the Distances, Transmission Rate, and Cable for Your Network Keywords: S7-200, Communication, Port, Cable Lengths, Pins May 2008
As shown in the table below, the maximum length of a network segment is determined by two factors: isolation (using an RS-485 repeater) and baud rate.
Isolation is required when you connect devices at different potentials. Different reference potentials can exist when grounds are physically separated by a long distance. Even over short distances, load currents of heavy machinery can cause a difference in ground potential.

Baud Rate Non-Isolated CPU Port CPU Port with Repeater or EM 277
9.6 kbaud to 187.5 kbaud 50 m 1000 m
500 kbaud Not supported 400 m
1 Mbaud to 1.5 Mbaud Not supported 200 m
3 Mbaud to 12 Mbaud Not supported 100 m

** The maximum distance allowed without using an isolator or repeater is 50 m. You measure this distance from the first node to the last node in the segment.

S7-200 networks use the RS-485 standard on twisted pair cables. The following table lists the specifications for the network cable. You can connect up to 32 devices on a network segment.

Specifications Description
Cable typeShielded, twisted pair
Loop resistance£115 W/km
Effective capacitance30 pF/m
Nominal impedenceApproximately 135 W to 160 W (frequency = 3MHz to 20 MHz)
Attuenuation0.9 dB/100 m (frequency=200 kHz)
Cress-sectional core area0.3mm2 to 0.5 mm2
Cable diameter8 mm +0.5 mm


Connector Pin Assignments

The communication ports on the S7-200 CPUs are RS-485 compatible on a nine-pin subminiature D connector in accordance with the PROFIBUS standard as defined in the European Standard EN 50170. The table below shows the connector that provides the physical connection for the communication port and describes the communication port pin assignments.

Pin NumberSignal Port 0/Port 1
1ShieldChassis ground
224V ReturnLogic common
3RS-485 Signal BRS-485 Signal B
4Request-to-sendRTS(TTL)
55V ReturnLogic common
6+5V+5V, 100W series resistor
7+24V+24V
8RS-485 Signal ARS-485 Signal A
9Not applicable10-bit protocol select (input)
Connector shellShieldChassis ground